Add to MyChemicals Print Friendly Page
Chemical Datasheet

FUEL OIL, [DIESEL]

3 - Flammable liquid
Chemical Identifiers | Hazards | Response Recommendations | Physical Properties | Regulatory Information | Alternate Chemical Names

Chemical Identifiers

The Chemical Identifier fields include common identification numbers, the NFPA diamond, U.S. Department of Transportation hazard labels, and a general description of the chemical. The information in CAMEO Chemicals comes from a variety of data sources..
CAS Number UN/NA Number DOT Hazard Label USCG CHRIS Code
  • 68334-30-5
  • 68476-30-2
  • 68476-31-3
  • 68476-34-6
  • 77650-28-3
  • Flammable Liquid
NFPA 704
Diamond Hazard Value Description
2
1 0
Blue Health 1 Can cause significant irritation.
Red Flammability 2 Must be moderately heated or exposed to relatively high ambient temperatures before ignition can occur.
Yellow Instability 0 Normally stable, even under fire conditions.
White Special
(NFPA, 2010)
NIOSH Pocket Guide International Chem Safety Card
none
General Description
A straw yellow to dark colored liquid with a petroleum-like odor. Flash point below 141°F. Less dense than water and insoluble in water. Hence floats on water. Vapors heavier than air.

Hazards

The Hazard fields include special hazard alerts, air and water reactions, fire hazards, health hazards, a reactivity profile, and details about reactive groups assignments and potentially incompatible absorbents. The information in CAMEO Chemicals comes from a variety of data sources.
Reactivity Alerts
Air & Water Reactions
Flammable. Insoluble in water.
Fire Hazard
Combustible. (USCG, 1999)
Health Hazard
LIQUID: Irritating to skin and eyes. Harmful if swallowed. (USCG, 1999)
Reactivity Profile
Saturated aliphatic hydrocarbons, which are contained in FUEL OIL, [DIESEL], may be incompatible with strong oxidizing agents like nitric acid. Charring of the hydrocarbon may occur followed by ignition of unreacted hydrocarbon and other nearby combustibles. In other settings, aliphatic saturated hydrocarbons are mostly unreactive. They are not affected by aqueous solutions of acids, alkalis, most oxidizing agents, and most reducing agents. When heated sufficiently or when ignited in the presence of air, oxygen or strong oxidizing agents, they burn exothermically to produce carbon dioxide and water. May be ignited by strong oxidizers.
Belongs to the Following Reactive Group(s)
Potentially Incompatible Absorbents

No information available.

Response Recommendations

The Response Recommendation fields include isolation and evacuation distances, as well as recommendations for firefighting, non-fire response, protective clothing, and first aid. The information in CAMEO Chemicals comes from a variety of data sources.
Isolation and Evacuation
Excerpt from ERG Guide 128 [Flammable Liquids (Water-Immiscible)]:

As an immediate precautionary measure, isolate spill or leak area for at least 50 meters (150 feet) in all directions.

LARGE SPILL: Consider initial downwind evacuation for at least 300 meters (1000 feet).

FIRE: If tank, rail car or tank truck is involved in a fire, ISOLATE for 800 meters (1/2 mile) in all directions; also, consider initial evacuation for 800 meters (1/2 mile) in all directions. (ERG, 2016)
Firefighting
Excerpt from ERG Guide 128 [Flammable Liquids (Water-Immiscible)]:

CAUTION: All these products have a very low flash point: Use of water spray when fighting fire may be inefficient. CAUTION: For mixtures containing alcohol or polar solvent, alcohol-resistant foam may be more effective.

SMALL FIRE: Dry chemical, CO2, water spray or regular foam.

LARGE FIRE: Water spray, fog or regular foam. Do not use straight streams. Move containers from fire area if you can do it without risk.

FIRE INVOLVING TANKS OR CAR/TRAILER LOADS: Fight fire from maximum distance or use unmanned hose holders or monitor nozzles. Cool containers with flooding quantities of water until well after fire is out. Withdraw immediately in case of rising sound from venting safety devices or discoloration of tank. ALWAYS stay away from tanks engulfed in fire. For massive fire, use unmanned hose holders or monitor nozzles; if this is impossible, withdraw from area and let fire burn. (ERG, 2016)
Non-Fire Response
Excerpt from ERG Guide 128 [Flammable Liquids (Water-Immiscible)]:

ELIMINATE all ignition sources (no smoking, flares, sparks or flames in immediate area). All equipment used when handling the product must be grounded. Do not touch or walk through spilled material. Stop leak if you can do it without risk. Prevent entry into waterways, sewers, basements or confined areas. A vapor-suppressing foam may be used to reduce vapors. Absorb or cover with dry earth, sand or other non-combustible material and transfer to containers. Use clean, non-sparking tools to collect absorbed material.

LARGE SPILL: Dike far ahead of liquid spill for later disposal. Water spray may reduce vapor, but may not prevent ignition in closed spaces. (ERG, 2016)
Protective Clothing
Excerpt from ERG Guide 128 [Flammable Liquids (Water-Immiscible)]:

Wear positive pressure self-contained breathing apparatus (SCBA). Structural firefighters' protective clothing will only provide limited protection. (ERG, 2016)
DuPont Tychem® Suit Fabrics
Tychem® Fabric Legend
QC = Tychem QC
SL = Tychem SL
TF = Tychem F
TP = Tychem ThermoPro
C3 = Tychem CPF 3
BR = Tychem BR
RC = Tychem Responder® CSM
TK = Tychem TK
RF = Tychem Reflector®
Testing Details
Permeation data obtained per ASTM F739. Normalized breakthrough times (the time at which the permeation rate is equal to 0.1 µg/cm2/min) reported in minutes. All liquid chemicals have been tested between approximately 20°C and 27°C unless otherwise stated. All chemicals have been tested at a concentration of greater than 95% unless otherwise stated. Chemical warfare agents (Lewisite, Sarin, Soman, Sulfur Mustard, Tabun and VX Nerve Agent) have been tested at 22°C and 50% relative humidity per military standard MIL-STD-282.
Normalized Breakthrough Times (in Minutes)
Chemical CAS Number State QC SL TF TP C3 BR RC TK RF
Diesel fuel 68334-30-5 Liquid 48 >480 >480 199 >480 >480 >480 >480
Fuel oil 68476-30-2 Liquid imm. >480 >480
> indicates greater than.
"imm." indicates immediate; having a normalized breakthrough time of 10 minutes or less.
A blank cell indicates the fabric has not been tested. The fabric may or may not offer barrier.

Special Warnings from DuPont

  1. Serged and bound seams are degraded by some hazardous liquid chemicals, such as strong acids, and should not be worn when these chemicals are present.
  2. CAUTION: This information is based upon technical data that DuPont believes to be reliable. It is subject to revision as additional knowledge and experience are gained. DuPont makes no guarantee of results and assumes no obligation or liability...
    ... in connection with this information. It is the user's responsibility to determine the level of toxicity and the proper personal protective equipment needed. The information set forth herein reflects laboratory performance of fabrics, not complete garments, under controlled conditions. It is intended for informational use by persons having technical skill for evaluation under their specific end-use conditions, at their own discretion and risk. Anyone intending to use this information should first verify that the garment selected is suitable for the intended use. In many cases, seams and closures have shorter breakthrough times and higher permeation rates than the fabric. Please contact DuPont for specific data. If fabric becomes torn, abraded or punctured, or if seams or closures fail, or if attached gloves, visors, etc. are damaged, end user should discontinue use of garment to avoid potential exposure to chemical. Since conditions of use are outside our control, we make no warranties, express or implied, including, without limitation, no warranties of merchantability or fitness for a particular use and assume no liability in connection with any use of this information. This information is not intended as a license to operate under or a recommendation to infringe any patent or technical information of DuPont or others covering any material or its use.

(DuPont, 2016)

First Aid
EYES: First check the victim for contact lenses and remove if present. Flush victim's eyes with water or normal saline solution for 20 to 30 minutes while simultaneously calling a hospital or poison control center. Do not put any ointments, oils, or medication in the victim's eyes without specific instructions from a physician. IMMEDIATELY transport the victim after flushing eyes to a hospital even if no symptoms (such as redness or irritation) develop.

SKIN: IMMEDIATELY flood affected skin with water while removing and isolating all contaminated clothing. Gently wash all affected skin areas thoroughly with soap and water. If symptoms such as redness or irritation develop, IMMEDIATELY call a physician and be prepared to transport the victim to a hospital for treatment.

INHALATION: IMMEDIATELY leave the contaminated area; take deep breaths of fresh air. If symptoms (such as wheezing, coughing, shortness of breath, or burning in the mouth, throat, or chest) develop, call a physician and be prepared to transport the victim to a hospital. Provide proper respiratory protection to rescuers entering an unknown atmosphere. Whenever possible, Self-Contained Breathing Apparatus (SCBA) should be used; if not available, use a level of protection greater than or equal to that advised under Protective Clothing.

INGESTION: DO NOT INDUCE VOMITING. If the victim is conscious and not convulsing, give 1 or 2 glasses of water to dilute the chemical and IMMEDIATELY call a hospital or poison control center. Be prepared to transport the victim to a hospital if advised by a physician. If the victim is convulsing or unconscious, do not give anything by mouth, ensure that the victim's airway is open and lay the victim on his/her side with the head lower than the body. DO NOT INDUCE VOMITING. IMMEDIATELY transport the victim to a hospital. (NTP, 1992)

Physical Properties

The Physical Property fields include properties such as vapor pressure and boiling point, as well as explosive limits and toxic exposure thresholds. The information in CAMEO Chemicals comes from a variety of data sources.
Chemical Formula: data unavailable
Flash Point: 125 ° F (NTP, 1992)
Lower Explosive Limit (LEL): 1.3 % (NTP, 1992)
Upper Explosive Limit (UEL): 6 % (NTP, 1992)
Autoignition Temperature: 350 to 625 ° F (USCG, 1999)
Melting Point: 0 ° F (NTP, 1992)
Vapor Pressure: 2.17 mm Hg at 70 ° F (USCG, 1999)
Vapor Density (Relative to Air): data unavailable
Specific Gravity: 0.841 at 60.8 ° F (USCG, 1999)
Boiling Point: 540 to 640 ° F at 760 mm Hg (NTP, 1992)
Molecular Weight: data unavailable
Water Solubility: less than 1 mg/mL at 66° F (NTP, 1992)
Ionization Potential: data unavailable
IDLH: data unavailable

AEGLs (Acute Exposure Guideline Levels)

No AEGL information available.

ERPGs (Emergency Response Planning Guidelines)

Chemical ERPG-1 ERPG-2 ERPG-3
Diesel Fuel and Other Middle Distillate Fuels (68334-30-5) 300 mg/m3 star-in-circle icon indicates that odor should be detectable near ERPG-1. 1000 mg/m3 Not Established
star-in-circle icon indicates that odor should be detectable near ERPG-1.
(AIHA, 2016)

PACs (Protective Action Criteria)

Chemical PAC-1 PAC-2 PAC-3
Diesel fuels; (includes diesel fuel No. 4 (68476-31-3), fuel oil No.2 (68476-30-2), fuel oil residual (68476-33-5) (68334-30-5) 300 mg/m3 3300 mg/m3 20000 mg/m3
(DOE, 2016)

Regulatory Information

The Regulatory Information fields include information from the U.S. Environmental Protection Agency's Title III Consolidated List of Lists and the U.S. Department of Homeland Security's Chemical Facility Anti-Terrorism Standards (see more about these data sources).

EPA Consolidated List of Lists

No regulatory information available.

DHS Chemical Facility Anti-Terrorism Standards (CFATS)

No regulatory information available.

Alternate Chemical Names

This section provides a listing of alternate names for this chemical, including trade names and synonyms.