Print
Chemical Datasheet
LIQUEFIED NATURAL GAS (CRYOGENIC LIQUID) |
|
Chemical Identifiers
CAS Number |
UN/NA Number |
DOT Hazard Label |
USCG CHRIS Code |
- 74-82-8
|
|
|
|
NIOSH Pocket Guide |
International Chem Safety Card |
none
|
|
NFPA 704
General Description
Methane is a colorless odorless gas. It is also known as marsh gas or methyl hydride. It is easily ignited. The vapors are lighter than air. Under prolonged exposure to fire or intense heat the containers may rupture violently and rocket. It is used in making other chemicals and as a constituent of the fuel, natural gas.
Hazards
Reactivity Alerts
Air & Water Reactions
Highly flammable.
Fire Hazard
Excerpt from ERG Guide 115 [Gases - Flammable (Including Refrigerated Liquids)]:
EXTREMELY FLAMMABLE. Will be easily ignited by heat, sparks or flames. Will form explosive mixtures with air. Vapors from liquefied gas are initially heavier than air and spread along ground. CAUTION: Hydrogen (UN1049), Deuterium (UN1957), Hydrogen, refrigerated liquid (UN1966), Methane (UN1971) and Hydrogen and Methane mixture, compressed (UN2034) are lighter than air and will rise. Hydrogen and Deuterium fires are difficult to detect since they burn with an invisible flame. Use an alternate method of detection (thermal camera, broom handle, etc.) Vapors may travel to source of ignition and flash back. Cylinders exposed to fire may vent and release flammable gas through pressure relief devices. Containers may explode when heated. Ruptured cylinders may rocket. CAUTION: When LNG - Liquefied natural gas (UN1972) is released on or near water, product may vaporize explosively. (ERG, 2024)
Health Hazard
If concentration of gas is high enough, may cause asphyxiation. No detectable systemic effects, even at 5% concentration in air. (USCG, 1999)
Reactivity Profile
Contact of very cold liquefied gas with water may result in vigorous or violent boiling of the product and extremely rapid vaporization due to the large temperature differences involved. If the water is hot, there is the possibility that a liquid "superheat" explosion may occur. Pressures may build to dangerous levels if liquid gas contacts water in a closed container [Handling Chemicals Safely 1980].
Belongs to the Following Reactive Group(s)
- Hydrocarbons, Aliphatic Saturated
Potentially Incompatible Absorbents
No information available.
Response Recommendations
Isolation and Evacuation
Excerpt from ERG Guide 115 [Gases - Flammable (Including Refrigerated Liquids)]:
IMMEDIATE PRECAUTIONARY MEASURE: Isolate spill or leak area for at least 100 meters (330 feet) in all directions.
LARGE SPILL: Consider initial downwind evacuation for at least 800 meters (1/2 mile).
FIRE: If tank, rail tank car or highway tank is involved in a fire, ISOLATE for 1600 meters (1 mile) in all directions; also, consider initial evacuation for 1600 meters (1 mile) in all directions. In fires involving Liquefied Petroleum Gases (LPG) (UN1075), Butane (UN1011), Butylene (UN1012), Isobutylene (UN1055), Propylene (UN1077), Isobutane (UN1969), and Propane (UN1978), also refer to the "BLEVE - Safety Precautions" section. (ERG, 2024)
Firefighting
Excerpt from ERG Guide 115 [Gases - Flammable (Including Refrigerated Liquids)]:
DO NOT EXTINGUISH A LEAKING GAS FIRE UNLESS LEAK CAN BE STOPPED. CAUTION: Hydrogen (UN1049), Deuterium (UN1957), Hydrogen, refrigerated liquid (UN1966) and Hydrogen and Methane mixture, compressed (UN2034) will burn with an invisible flame. Use an alternate method of detection (thermal camera, broom handle, etc.).
SMALL FIRE: Dry chemical or CO2.
LARGE FIRE: Water spray or fog. If it can be done safely, move undamaged containers away from the area around the fire. CAUTION: For LNG - Liquefied natural gas (UN1972) pool fires, DO NOT USE water. Use dry chemical or high-expansion foam.
FIRE INVOLVING TANKS: Fight fire from maximum distance or use unmanned master stream devices or monitor nozzles. Cool containers with flooding quantities of water until well after fire is out. Do not direct water at source of leak or safety devices; icing may occur. Withdraw immediately in case of rising sound from venting safety devices or discoloration of tank. ALWAYS stay away from tanks in direct contact with flames. For massive fire, use unmanned master stream devices or monitor nozzles; if this is impossible, withdraw from area and let fire burn. (ERG, 2024)
Non-Fire Response
Excerpt from ERG Guide 115 [Gases - Flammable (Including Refrigerated Liquids)]:
ELIMINATE all ignition sources (no smoking, flares, sparks or flames) from immediate area. All equipment used when handling the product must be grounded. Do not touch or walk through spilled material. Stop leak if you can do it without risk. If possible, turn leaking containers so that gas escapes rather than liquid. Use water spray to reduce vapors or divert vapor cloud drift. Avoid allowing water runoff to contact spilled material. Do not direct water at spill or source of leak. CAUTION: For LNG - Liquefied natural gas (UN1972), DO NOT apply water, regular or alcohol-resistant foam directly on spill. Use a high-expansion foam if available to reduce vapors. Prevent spreading of vapors through sewers, ventilation systems and confined areas. Isolate area until gas has dispersed. CAUTION: When in contact with refrigerated/cryogenic liquids, many materials become brittle and are likely to break without warning. (ERG, 2024)
Protective Clothing
Self-contained breathing apparatus; protective clothing if exposed to liquid. (USCG, 1999)
DuPont Tychem® Suit Fabrics
No information available.
First Aid
Remove victim to open air. If he is overcome by gas, apply artificial resuscitation. (USCG, 1999)
Physical Properties
Flash Point: data unavailable
Lower Explosive Limit (LEL):
5.3 %
(USCG, 1999)
Upper Explosive Limit (UEL):
14 %
(USCG, 1999)
Autoignition Temperature:
999°F
(USCG, 1999)
Melting Point:
-296°F
(USCG, 1999)
Vapor Pressure: data unavailable
Vapor Density (Relative to Air): data unavailable
Specific Gravity:
0.415 to 0.45
at -259.6°F
(USCG, 1999)
Boiling Point:
-258°F
at 760 mmHg
(USCG, 1999)
Molecular Weight:
greater than 16
(USCG, 1999)
Water Solubility: data unavailable
Ionization Energy/Potential: data unavailable
IDLH: data unavailable
AEGLs (Acute Exposure Guideline Levels)
No AEGL information available.
ERPGs (Emergency Response Planning Guidelines)
No ERPG information available.
Regulatory Information
EPA Consolidated List of Lists
Regulatory Name |
CAS Number/ 313 Category Code |
EPCRA 302 EHS TPQ |
EPCRA 304 EHS RQ |
CERCLA RQ |
EPCRA 313 TRI |
RCRA Code |
CAA 112(r) RMP TQ |
Methane |
74-82-8 |
|
|
|
|
|
10000 pounds |
(EPA List of Lists, 2024)
CISA Chemical Facility Anti-Terrorism Standards (CFATS)
|
RELEASE |
THEFT |
SABOTAGE |
Chemical of Interest |
CAS Number |
Min Conc |
STQ |
Security Issue |
Min Conc |
STQ |
Security Issue |
Min Conc |
STQ |
Security Issue |
Methane |
74-82-8 |
1.00 % |
10000 pounds |
flammable |
|
|
|
|
|
|
(CISA, 2007)
OSHA Process Safety Management (PSM) Standard List
No regulatory information available.
Alternate Chemical Names
- LIQUEFIED NATURAL GAS
- LIQUEFIED NATURAL GAS (CRYOGENIC LIQUID)
- LNG
- LNG (CRYOGENIC LIQUID)
- NATURAL GAS, LIQUIFIED