Print
Chemical Datasheet

N-PROPANOL

3 - Flammable liquid

Chemical Identifiers

CAS Number UN/NA Number DOT Hazard Label USCG CHRIS Code
  • 71-23-8   (N-PROPANOL)
  • 1274
  • Flammable Liquid
  • PAL
NIOSH Pocket Guide International Chem Safety Card
n-Propyl alcohol
  • 1-PROPANOL
NFPA 704
Diamond Hazard Value Description
3
1 0
Blue Health 1 Can cause significant irritation.
Red Flammability 3 Can be ignited under almost all ambient temperature conditions.
Yellow Instability 0 Normally stable, even under fire conditions.
White Special
(NFPA, 2010)
General Description
A clear colorless liquid with a sharp musty odor like rubbing alcohol. Flash point 53-77°F. Autoignites at 700°F. Vapors are heavier than air and mildly irritate the eyes, nose, and throat. Density approximately 6.5 lb / gal. Used in making cosmetics, skin and hair preparations, pharmaceuticals, perfumes, lacquer formulations, dye solutions, antifreezes, rubbing alcohols, soaps, window cleaners, acetone and other chemicals and products.

Hazards

Reactivity Alerts
Air & Water Reactions
Highly flammable. Water soluble.
Fire Hazard
Excerpt from 129 Polymerizable warning [Flammable Liquids (Water-Miscible / Noxious)]:

HIGHLY FLAMMABLE: Will be easily ignited by heat, sparks or flames. Vapors may form explosive mixtures with air. Vapors may travel to source of ignition and flash back. Most vapors are heavier than air. They will spread along the ground and collect in low or confined areas (sewers, basements, tanks, etc.). Vapor explosion hazard indoors, outdoors or in sewers. Those substances designated with a (P) may polymerize explosively when heated or involved in a fire. Runoff to sewer may create fire or explosion hazard. Containers may explode when heated. Many liquids will float on water. (ERG, 2020)
Health Hazard
Contact with eyes is extremely irritating and may cause burns. Vapors irritate nose and throat. In high concentrations, may cause nausea, dizziness, headache, and stupor. (USCG, 1999)
Reactivity Profile
N-PROPANOL reacts with alkali metal, nitrides and strong reducing agents to give flammable and/or toxic gases. Reacts with oxoacids and carboxylic acids to form esters plus water. Converted by oxidizing agents to propanal or propionic acid. May initiate the polymerization of isocyanates and epoxides.

Incompatible with strong oxidizing agents (NIOSH, 2022).
Belongs to the Following Reactive Group(s)
Potentially Incompatible Absorbents

Use caution: Liquids with this reactive group classification have been known to react with the absorbent listed below.

Response Recommendations

Isolation and Evacuation
Excerpt from 129 Polymerizable warning [Flammable Liquids (Water-Miscible / Noxious)]:

IMMEDIATE PRECAUTIONARY MEASURE: Isolate spill or leak area for at least 50 meters (150 feet) in all directions.

LARGE SPILL: Consider initial downwind evacuation for at least 300 meters (1000 feet).

FIRE: If tank, rail car or tank truck is involved in a fire, ISOLATE for 800 meters (1/2 mile) in all directions; also, consider initial evacuation for 800 meters (1/2 mile) in all directions. (ERG, 2020)
Firefighting
Excerpt from 129 Polymerizable warning [Flammable Liquids (Water-Miscible / Noxious)]:

CAUTION: The majority of these products have a very low flash point. Use of water spray when fighting fire may be inefficient.

SMALL FIRE: Dry chemical, CO2, water spray or alcohol-resistant foam. Do not use dry chemical extinguishers to control fires involving nitromethane (UN1261) or nitroethane (UN2842).

LARGE FIRE: Water spray, fog or alcohol-resistant foam. Avoid aiming straight or solid streams directly onto the product. If it can be done safely, move undamaged containers away from the area around the fire.

FIRE INVOLVING TANKS OR CAR/TRAILER LOADS: Fight fire from maximum distance or use unmanned master stream devices or monitor nozzles. Cool containers with flooding quantities of water until well after fire is out. Withdraw immediately in case of rising sound from venting safety devices or discoloration of tank. ALWAYS stay away from tanks engulfed in fire. For massive fire, use unmanned master stream devices or monitor nozzles; if this is impossible, withdraw from area and let fire burn. (ERG, 2020)
Non-Fire Response
Excerpt from 129 Polymerizable warning [Flammable Liquids (Water-Miscible / Noxious)]:

ELIMINATE all ignition sources (no smoking, flares, sparks or flames) from immediate area. All equipment used when handling the product must be grounded. Do not touch or walk through spilled material. Stop leak if you can do it without risk. Prevent entry into waterways, sewers, basements or confined areas. A vapor-suppressing foam may be used to reduce vapors. Absorb or cover with dry earth, sand or other non-combustible material and transfer to containers. Use clean, non-sparking tools to collect absorbed material.

LARGE SPILL: Dike far ahead of liquid spill for later disposal. Water spray may reduce vapor, but may not prevent ignition in closed spaces. (ERG, 2020)
Protective Clothing
Excerpt from NIOSH Pocket Guide for n-Propyl alcohol:

Skin: PREVENT SKIN CONTACT - Wear appropriate personal protective clothing to prevent skin contact.

Eyes: PREVENT EYE CONTACT - Wear appropriate eye protection to prevent eye contact.

Wash skin: WHEN CONTAMINATED - The worker should immediately wash the skin when it becomes contaminated.

Remove: WHEN WET (FLAMMABLE) - Work clothing that becomes wet should be immediately removed due to its flammability hazard (i.e., for liquids with a flash point <100°F).

Change: No recommendation is made specifying the need for the worker to change clothing after the workshift. (NIOSH, 2023)
DuPont Tychem® Suit Fabrics
Normalized Breakthrough Times (in Minutes)
Chemical CAS Number State QS QC SL C3 TF TP RC TK RF
Propan -1-ol 71-23-8 Liquid >480 >480
Propanol, 1- 71-23-8 Liquid >480 >480
Propanol, n- 71-23-8 Liquid >480 >480
Propyl alcohol 71-23-8 Liquid >480 >480
> indicates greater than.

Special Warning from DuPont: Tychem® and Tyvek® fabrics should not be used around heat, flames, sparks or in potentially flammable or explosive environments. Only...

(DuPont, 2023)

First Aid
Excerpt from NIOSH Pocket Guide for n-Propyl alcohol:

Eye: IRRIGATE IMMEDIATELY - If this chemical contacts the eyes, immediately wash (irrigate) the eyes with large amounts of water, occasionally lifting the lower and upper lids. Get medical attention immediately.

Skin: WATER FLUSH - If this chemical contacts the skin, flush the contaminated skin with water. Where there is evidence of skin irritation, get medical attention.

Breathing: RESPIRATORY SUPPORT - If a person breathes large amounts of this chemical, move the exposed person to fresh air at once. If breathing has stopped, perform artificial respiration. Keep the affected person warm and at rest. Get medical attention as soon as possible.

Swallow: MEDICAL ATTENTION IMMEDIATELY - If this chemical has been swallowed, get medical attention immediately. (NIOSH, 2023)

Physical Properties

Chemical Formula:
  • C3H8O
Flash Point: 77°F (USCG, 1999)
Lower Explosive Limit (LEL): 2.1 % (USCG, 1999)
Upper Explosive Limit (UEL): 13.5 % (USCG, 1999)
Autoignition Temperature: 700°F (USCG, 1999)
Melting Point: -195.2°F (USCG, 1999)
Vapor Pressure: 44.98 mmHg (USCG, 1999)
Vapor Density (Relative to Air): data unavailable
Specific Gravity: 0.803 at 68°F (USCG, 1999) - Less dense than water; will float
Boiling Point: 207°F at 760 mmHg (USCG, 1999)
Molecular Weight: 60.1 (USCG, 1999)
Water Solubility: Miscible (NIOSH, 2023)
Ionization Energy/Potential: 10.15 eV (NIOSH, 2023)
IDLH: 800 ppm (NIOSH, 2023)

AEGLs (Acute Exposure Guideline Levels)

No AEGL information available.

ERPGs (Emergency Response Planning Guidelines)

No ERPG information available.

PACs (Protective Action Criteria)

Chemical PAC-1 PAC-2 PAC-3
n-Propanol (Propyl alcohol, n-) (71-23-8) 250 ppm 670 ppm 4000 ppm 1-flame icon indicates value is 10-49% of LEL. LEL = 22000 ppm
1-flame icon indicates value is 10-49% of LEL.
(DOE, 2018)

Regulatory Information

EPA Consolidated List of Lists

No regulatory information available.

CISA Chemical Facility Anti-Terrorism Standards (CFATS)

No regulatory information available.

OSHA Process Safety Management (PSM) Standard List

No regulatory information available.

Alternate Chemical Names